Valjaonica - FEMOD d.o.o. Sevojno



Production programme

Oil-water radiators for energy transformers



Heat exchangers are made from high-finned copper tubes in a “chess-like” layout.

Fins are made of aluminium, and finning type determined in accordance with working conditions, (see the catalogue of finned tubing).

Heat exchanger size is determined on the basis of required capacity, avaialable accomodation space and special customers requirements.

Heat exchangers power ranges from 50 to 1000 kW.

The same or similar construction is used for cooling of generator stator windings.

Oil-water radiators for energy transformers

Oil-water radiators for energy transformers

POSITIONS:
1 - Manifold (collector)
2 - Radiator body
3 - Radiator enclosure
4 - Fan


Type of Cooling Radiator power kW SIZES Total weight kg Fan unit Outside connections Noise dB
A
mm
B
mm
C
mm
D
mm
Number Power kW
HTU 175 175 2600 894 742 314 1250 2 1.1 PM16, DN125 75
HTU 225 225 3554 785 808 278 1400 2 1.1 PM16, DN125 75
HTU 300 300 3554 815 980 305 1600 3 1.1 PM16, DN125 80
HTU 380 380 3554 890 980 340 1800 3 1.1 PM16, DN125 80
HTU 400 400 3554 890 980 340 1900 3 1.1 PM16, DN125 80

PRIMERI


Oil-water radiators for energy transformers Oil-water radiators for energy transformers Oil-water radiators for energy transformers
Transformer 400 MVA
TENT Obrenovac
Transformer 150 MVA
TS Jajinci
Transformer 100 MVA
"TOPLANA" Beograd
Producer: "MINEL - TRANSFORMATORI" - Ripanj Srbija

©2007 Copyright by Valjaonica - FEMOD d.o.o. Sevojno. All rights reserved.
Member of Uzice.Net. Production: DataVoyage